SCH601MD
Airolite louver type SCH601MD is a sightproof, horizontal blade storm class Louver that is Florida Building Code approved for use in the High Velocity Hurricane Zone and Miami-Dade approved for installations where the enclosed space is designed to drain or otherwise accommodate water penetration (wet rooms).
Specifications
General | |
Beginning Point of Water Penetration | 1,250 fpm (6.35 m/s) |
Pressure Drop at Beginning Point of Water Penetration | 0.35 in. wg (0.087kPa) |
Test Standard | AMCA Standard 500-L Water Penetration, Air Performance and Wind Driven Rain, AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic Protection, Missile Level D and Enhanced Protection, Missile Level E), AMCA 550 High Velocity Rain Resistant (with factory attached VCD-40 Damper in closed position), Florida Test Protocol: TAS 201 Large Missile Impact, Florida Test Protocol: TAS 202 Uniform Static Air Pressure, Florida Test Protocol: TAS 203 Cyclic Wind Loading |
Percent Free Area | 45% (4 ft. x 4 ft.) |
Louver Depth | 6" (152.4 mm) |
Resources
Assistance
Our representatives can assists you in selecting the right product for your project. Contact us