SCC550MD

Airolite louver type SCC550MD is Florida Building Code Approved for use in the High Velocity Hurrican Zone and Miami-Dade Approved use for where the room behind the louver is not designed to drain water penetrating into the room will house non-water resistance or water proof equipment, components or supplies. The design incorporates exterior and interior louver modules that afford the designer optimum flexibility in aesthetic, economic and performance considerations.

Specifications Hide all

General
Beginning Point of Water Penetration 1,083 FPM (5.50 m/s)
Louver Depth 5.5 in. (140 mm)
Percent Free Area 50% (4 ft. x 4 ft.)
Pressure Drop at Beginning Point of Water Penetration 0.44 in. wg (0.109kPa)
Test Standard AMCA Standard 500-L Water Penetration, Air Performance and Wind Driven Rain, AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic Protection, Missile D and Enhanced Protection, Missile E), AMCA 550 High Velocity Wind Driven Rain, Florida Test Protocol: TAS 201 Large Missile Impact, Florida Test Protocol: TAS 202 Uniform Static Air Pressure, Florida Test Protocol: TAS 203 Cyclic Wind Loading

Assistance

Our representatives can assists you in selecting the right product for your project. Contact us