K6744X
Airolite louver type K6744X is a 4-inch (101.6 mm) deep, drainable louver that is Florida Building Code approved for use in the Wind-Borne Debris Zone and the High Velocity Hurricane Zone (HVHZ).
Specifications
General | |
Beginning Point of Water Penetration | 989 fpm (5.02 m/s) |
Pressure Drop at Beginning Point of Water Penetration | 0.16 in. wg (0.04kPa) |
Test Standard | AMCA Standard 500-L Water Penetration and Air Performance, AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic Protection, Missile D), Florida Test Protocol: TAS 201 Large Missile Impact, Florida Test Protocol: TAS 202 Uniform Static Air Pressure, Florida Test Protocol: TAS 203 Cyclic Wind Loading |
Percent Free Area | 56% (4 ft. x 4 ft.) |
Louver Depth | 4” (101.6 mm) |
Resources
Assistance
Our representatives can assists you in selecting the right product for your project. Contact us